G7TC
G7TC
- Compact size: 182 (W) ✕ 85 (D) ✕ 68 (H) mm (8-point Output Block width is 102 mm).
- Connects to the PLC through the connector, and requires only a snap-in operation.
- Surge suppressor circuit built-in.
- Immediate recognition of I/O signal status using LED operation indicators.
- G3TA I/O Solid-state relay can be mounted instead of G7T.
- Mounts easily on a DIN track.
- Approved by UL, CSA (except for G7TC-OC16-1).
Specifications & ordering info
Ordering Information
I/O Relay Terminal
I/O classification | I/O points | Internal I/O common | Rated voltage | Order code |
---|---|---|---|---|
Input | 16 | NPN (– common) | 12 VDC | G7TC-ID16 |
24 VDC | ||||
100 (110) VDC | ||||
100/(110) VAC | G7TC-IA16 | |||
200/(220) VAC | ||||
Output | 16 | NPN (+ common) | 12 VDC | G7TC-OC16 |
24 VDC | ||||
PNP (– common) | 12 VDC | G7TC-OC16-1
2
Not
approved by UL, CSA. |
||
24 VDC | ||||
8 | NPN (+ common) | 12 VDC | G7TC-OC08 | |
24 VDC |
- When ordering, add the rated coil voltage to the model number. Example: G7TC-ID1 24 VDC
- When the G7TC is used with an AC rated voltage, three rated currents can be used. If a coil voltage of 110 or 220 VAC is used, 50 Hz cannot be used.
Accessories (Order Separately)
Cable for I/O Relay Terminals XW2Z-R
Type | Order code | ||
---|---|---|---|
Cable with Loose Wire and Crimp Terminals | XW2Z-RY |
||
Cable with Loose Wires | XW2Z-RA |
||
Cable with connectors | Fujitsu connectors | (1:1) | XW2Z-R |
(1:2) | XW2Z-RI |
||
XW2Z-RO |
|||
(1:3) | XW2Z-R |
||
MIL connectors | (1:1) | XW2Z-RI |
|
XW2Z-RO |
|||
(1:2) | XW2Z-RI |
||
XW2Z-RM |
|||
XW2Z-RO |
Refer to Connecting Cables for details.
Short Bar
Item | Order code |
---|---|
Short Bar | G78-04 |
Output Short-Circuit Module
Item | Order code |
---|---|
Output Short-Circuit Module | G77-S |
Socket
Item | Order code |
---|---|
Socket | P7TF-05 |
Mounted Relays and I/O Terminal Sockets
Mounted Relays (G7T I/O Relays and G3TA I/O SSRs)
I/O Terminal Sockets (P7TF-IS16/OS16/OS08)
Refer to Safety Precautions for details.
Indicator Module (With Surge Suppressing Function)
Applicable relay coil voltage | Remarks | Order code | |
---|---|---|---|
For AC relay | 100 (110) V AC | Varistor surge suppression | P70A |
200 (220) V AC | |||
For DC relay | 12/24 V DC | Diode surge suppression | P70D |
- Order the indicator module suitable for the relay coil voltage.
- The indicator module for DC relays can be used with a 12-V or 24 V DC power supply.
Accessories for DIN Track Mounting
Appearance | Name | Minimum order (quantity) | Order code | |
---|---|---|---|---|
![]() |
DIN Tracks | 1 m | 1 | PFP-100N |
0.5 m | PFP-50N | |||
![]() |
End Plate | 10 | PFP-M
2
Please order
in sets of 10 units. |
|
![]() |
Spacer | PFP-S
2
Please order
in sets of 10 units. |
Specifications
Coil Ratings (Common to Input/Output per Relay)
Item | Rated current (mA) | Coil resistance (Ω) |
Must operate |
Must release |
Maximum voltage |
Power consumption | |||
---|---|---|---|---|---|---|---|---|---|
Rated voltage (V) | 50 Hz | 60 Hz | of rated voltage | per Relay | per 16 Relays | ||||
AC | 100/(110) | 8.2/– | 7/7.7 | 8,700 | 80% max. | 30% min. | 105% | 0.7 VA | 11 VA |
200/(220) | 4.1/– | 3.5/3.85 | 33,300 | ||||||
DC | 12 | 42 | 290 | 80% max. | 10% min. | 105% | 0.5 W | 8 W | |
24 | 21 | 1,150 | |||||||
100/110 | 5 | 20,000 |
- The rated current and coil resistance are measured at a coil temperature of 23°C with a tolerance of 15%/-20% for AC rated current and ±15% for coil resistance.
- The operating characteristics are measured at a coil temperature of 23°C.
- The value for maximum voltage is the maximum value within the allowable voltage fluctuation range for the relay coil’s operating power supply. Continuous operation at this voltage is not within product specifications.
- Approx. 4 mA flows into each LED indicator. To calculate the power supply capacity, add the current value of each LED indicator.
- When the G7TC is used with an AC rated voltage, three rated currents can be used. If a coil voltage of 110 or 220 VAC is used, 50 Hz cannot be used.
Contact Ratings (G7T I/O Relay)
Classification | For input | For output | ||
---|---|---|---|---|
Item | Resistive load (cos |
Inductive load (cos |
Resistive load (cos |
Inductive load (cos |
Rated load | 1 A at 24 VDC | 0.5 A at 24 VDC | 2 A at 220 VAC 5 A at 24 VDC |
1 A at 220 VAC 2 A at 24 VDC |
Rated carry current | 1 A | 5 A | ||
Max. switching voltage | 250 VAC, 125 VDC | |||
Max. switching current | 1 A | 0.5 A | 5 A | 2 A |
Error rate (reference
value)
2
The above values are for a switching frequency of 120
operations/min. |
100 μA at 1 V | 10 mA at 5 V | ||
Electrical endurance | 10,000,000 operations (at 10 mA) 50,000 operations (at 1 A) |
2,500,000 operations (at 10 mA) 20,000 operations (at 1 A) |
1,000,000 operations (under rated load) | |
Mechanical endurance | 50,000,000 operations |
Characteristics
Item | G7TC-IA16 (Input, AC coil) |
G7TC-ID16 (Input, DC coil) |
G7TC-OC16 (–1) (output, DC coil) |
G7TC-OC08 (output, DC coil) |
|
---|---|---|---|---|---|
Contact form | SPST-NO × 16 | SPST-NO × 8 | |||
Contact mechanism | Bifurcated crossbar contact | Single contact | |||
Contact material | Au cladding + Ag | AgInSn | |||
Contact resistance
2
Measurement:
1 A at 5 VDC. |
50 mΩ max. | ||||
Must Operate
time
2
Ambient temperature: 23°C. |
15 ms max. | ||||
Release time
2
Ambient temperature: 23°C. |
15 ms max. | ||||
Max. switching frequency |
Mechanical limit | 18,000 operations/h | |||
At rated load | 1,800 operations/h | ||||
Insulation resistance | 100 MΩ (at 500 VDC) | ||||
Dielectric strength |
Between coil and contact | 2,000 VAC, 50/60 Hz for 1 minute | |||
Between same polarity contacts | 1,000 VAC, 50/60 Hz for 1 minute | ||||
Between paired connectors
2
This
is between connector pin No. 10 and 20, and between connector pin
No. 9 and 19. |
250 VAC, 50/60 Hz for 1 minute | ||||
Vibration resistance | 10 to 55 to 10 Hz with 0.5-mm single amplitude (1.0-mm double amplitude) | ||||
Shock resistance | 200 m/s2 | ||||
Noise immunity | Noise level: 1.5 kV; pulse width: 100 ns to 1 μs | ||||
Rated voltage between positive and negative terminal blocks |
Rated voltage of controller’s (PLC or other) input circuit |
12 VDC ±5% 24 VDC ±5% |
|||
Rated current between positive and negative terminal blocks |
Input circuit current of controller (PLC or other) × number of ON points |
12 VDC: 46 mA × number of ON points 24 VDC: 25 mA × number of ON points |
|||
Cable length
2
Connecting
cables up to 5 m are available as standard products. For longer
cables, enquire separately. |
To controller | 5 m max. (reference value) | |||
To I/O devices | 50 m max. (reference value, for 2-mm2 CVV cable) | Dependent on load | |||
Ambient operating temperature | 0 to 55°C | ||||
Ambient operating humidity | 35% to 85% (with no icing or condensation) | ||||
Tightening torque for external connections | 0.78 to 1.18 N·m | ||||
Tensile strength | No damage when a tensile force of 49 N is applied in each direction. In the direction of the track, the tensile strength is 9.8 N min. |
||||
I/O terminal tightening torque | Tightening strength: 0.98 N·m; Tensile strength 49 N per minute | ||||
LED color | Red | Green | |||
Case color | Transparent red | Transparent green | Transparent green | ||
Coil surge absorber | Varistor | Diode (1 A, 1,000 V) | |||
Weight | Approx. 640 g | Approx. 630 g | Approx. 670 g | Approx. 350 g |
The above values are initial values.
Approved Standards
- The rated values for safety standard certification are not the same as individually defined performance values. Always check the specifications before use.
- Standard G7TC I/O Relay Terminal, except for the G7TC-OC16-1 and the G7TC-OC08, have met UL and CSA standards (UL file no. E95399; CSA file no. LR35535).
UL standard certification (File No. E95399)
Model | Standard number | Category | Listed/Recognized | Contact ratings |
---|---|---|---|---|
G7TC-ID16 G7TC-IA16 |
UL508 | NRAQ2 | Recognized |
Terminal block side: 250 VAC max./point Connector side: 10 mA/point, 24 VDC |
G7TC-OC16 | UL508 | NRAQ2 | Recognized |
Terminal block side: Inductive load: 10 A, 250 VAC Resistive load: 10 A, 30 VDC Rated horsepower: 1/2 HP, 240 VAC |
CSA Standard (File No. LR35535)
Model | Standard number | Class number | Contact ratings |
---|---|---|---|
G7TC-ID16 |
CSA C22.2 No.14 |
3211 04 |
6 to 240 VAC 6 to 125 VDC |
G7TC-IA16 | |||
G7TC-OC16 |
How can we help you?
If you have a question or would like to ask for a quote, please contact us or send a request.
Kontakt meg G7TC

Takk for din forespørsel. Vi vil kontakte deg så snart som mulig.
Vi har for tiden tekniske problemer. Ditt skjema har ikke blitt innsendt. Vi beklager så mye og håper du vil prøve igjen senere. Detaljer:
DownloadTilbud for G7TC
Ved å fylle ut dette skjemaet vil du motta et tilbud på det valgte produktet. Vennligst fyll inn alle obligatoriske felter. Dine personlige opplysninger vil bli behandlet konfidensielt.

Takk for din tilbudsforespørsel. Vi vil sende deg det forespurte tilbudet så snart som mulig.
Vi har for tiden tekniske problemer. Ditt skjema har ikke blitt innsendt. Vi beklager så mye og håper du vil prøve igjen senere. Detaljer:
Download