Funksjoner

Kompakt strømrelé på 160 A

G7Z-serien gir en kompakt og kostnadseffektiv løsning for anvendelser som omformere, UPS og kretser for solceller og brenselceller. Relé i kombinasjon med hjelpekontaktkloss tilfredsstiller EN 60947-4-1. Mulige nominelle verdier for spoler er 12 og 24 VDC. Strømforbruket er mindre enn 4 watt.



  • Koblingsstrøm 160 A (40 A nominelt/4 poler / IEC-AC1)
  • Koblingsspenning 440 V vekselstrøm
  • Sikkerhetsfunksjon med speilkontakter i ulike konfigurasjoner
  • Strømforbruket er mindre enn 4 watt
  • Liten koblingsstøy (70 dB)
Spesifikasjoner & Bestillingsinfo

Ordering information

Relay with Auxiliary Contact Block (for Screw Terminals)

Contact configuration

Rated voltage

Order code

Relay

Auxiliary contact block

4PST-NO

DPST-NO

12, 24 VDC

G7Z-4A-20Z

SPST-NO/SPST-NC

G7Z-4A-11Z

DPST-NC

G7Z-4A-02Z

3PST-NO/SPST-NC

DPST-NO

G7Z-3A1B-20Z

SPST-NO/SPST-NC

G7Z-3A1B-11Z

DPST-NC

G7Z-3A1B-02Z

DPST-NO/DPST-NC

DPST-NO

G7Z-2A2B-20Z

SPST-NO/SPST-NC

G7Z-2A2B-11Z

DPST-NC

G7Z-2A2B-02Z

Specifications

Coil ratings

Rated voltage

Rated current

Coil resistance

Must operate voltage

Must release voltage

Max. voltage

Power consumption (approx.)

% of rated voltage

12 VDC

333 mA

39 Ω

75% max.

10% min.

110%

Approx. 3.7 W

24 VDC

154 mA

156 Ω

  • Note • Rated current and coil resistance were measured at a coil temperature of 23°C with coil resistance of ±15%.
  • • Operating characteristics were measured at a coil temperature of 23°C.
  • • The maximum allowable voltage is the maximum value of the fluctuation range for the Relay coil operating power supply and was measured at an ambient temperature of 23°C.

Contact Ratings - Relay

Item

G7Z-4A-_Z, G7Z-3A1B-_Z, G7Z-2A2B-_Z

Resistive load

Inductive load cos phi = 0.3

Resistive load L/R = 1 ms

Contact structure

Double break

Contact material

Ag alloy

Rated load

NO

40 A at 440 VAC

22 A at 440 VAC

5 A at 110 VDC

NC

25 A at 440 VAC

10 A at 440 VAC

5 A at 110 VDC

Rated carry current

NO

40 A

22 A

5 A

NC

25 A

10 A

5 A

Maximum contact voltage

480 VAC

125 VDC

Maximum contact current

NO

40 A

NC

25 A

Maximum switching capacity

NO

17,600 VA

9,680 VA

550 W

NC

11,000 VA

4,400 VA

550 W

Failure rate P value (reference value)

2 A at 24 VDC

Note: The ratings for the auxiliary contact block mounted on the G7Z are the same as those for the G73Z auxiliary contact block.

Contact Ratings - Auxiliary Contact Block

Item

G7Z-4A-_Z, G7Z-3A1B-_Z, G7Z-2A2B-_Z

Resistive load

Inductive load cos phi = 0.3

Resistive load L/R = 1 ms

Contact structure

Double break

Contact material

Au clad + Ag

Rated load

1 A at 440 VAC

0.5 A at 440 VAC

5 A at 110 VDC

Rated carry current

1 A

Maximum contact voltage

480 VAC

125 VDC

Maximum contact current

1 A

Maximum switching capacity

440 VA

220 VA

110 W

Failure rate P value (reference value)

1 mA at 5 VDC

Har du et spørsmål?

Vi er klare til å hjelpe.

Kontakt oss

Abonner på produktoppdateringer

Nyhetsbrev om produkter, løsninger og tjenester, direkte i innboksen.

Takk for at du abonnerer på Omrons eNews. Du vil snart motta en e-post fra oss. Denne e-posten inneholder en link som aktiverer ditt abonnement. Denne metoden brukes på grunn av juridiske årsaker og til å se til at ingen kan misbruke din e-postadresse.

Vi har for tiden tekniske problemer. Ditt skjema har ikke blitt innsendt. Vi beklager så mye og håper du vil prøve igjen senere. Detaljer:

Download

Produktdokumentasjon

Last ned dataark, håndbøker og brosjyrer.

Bla gjennom nedlastingssenter

Opplæringskurs

Få opplæring fra våre beste ingeniører. Fra nybegynner til avansert nivå.

Vis opplæringskurs