K8AK-PM

Funksjoner

3-fasespenning, fasesekvens, fasetapsrelé

K8AK-PM gir overvåking av overspenning, underspenning, fasesekvens og fasetap for trefasede tretråds eller firetråds strømforsyninger i én enhet. Dette releet har en omkobling for trefasede tretråds eller trefasede firetråds strømforsyninger.
  • Verdensomfattende strømspesifikasjoner støttes av en enhet
  • Fasesekvens, fasetap: driftsreaksjonstid maks. 0,1 s
  • Overspenning eller underspenning: driftstidsinnstilling fra 0,1 til 30 s
  • Status for relévarsling kan lett overvåkes ved hjelp av LED-indikatoren.
  • Enkel ledningstilkobling med eller uten endehylser
Spesifikasjoner & Bestillingsinfo

Ordering information

Rated input

Order code

3-phase 3-wire mode

200, 220, 230, 240 VAC

K8AK-PM1

3-phase 4-wire mode

115, 127, 133, 138 VAC

3-phase 3-wire mode

380, 400, 415, 480 VAC

K8AK-PM2

3-phase 4-wire mode

220, 230, 240, 277 VAC

Specifications

Ambient operating temperature

-20 to 60°C (with no condensation or icing)

Storage temperature

-25 to 65°C (with no condensation or icing)

Input frequency

50/60 Hz (AC power supply)

Output relays
(2 × SPDT, normally closed operation)

Resistive load

5 A at 250 VAC or at 30 VDC

Maximum contact voltage

250 VAC or 30 VDC

Maximum contact current

5 A

Maximum switching capacity

1,250 VA, 150 W

Mechanical life

10,000,000 operations

Electrical life

50,000 operations at 5 A, 250 VAC or 30 VDC

Degree of protection

Terminal section: IP20

Case material

PC and ABS

Weight

Approx. 150 g

Rated input voltage

K8AK-PM1

3-phase, 3-wire mode: 200, 220, 230, 240 VAC, 3-phase, 4-wire mode: 115, 127, 133, 138 VAC

K8AK-PM2

3-phase, 3-wire mode: 380, 400, 415, 480 VAC, 3-phase, 4-wire mode: 220, 230, 240, 277 VAC

Operation (overvoltage or undervoltage)

Operating value setting range

Overvoltage = -30% to 25% of maximum rated input voltage1

Undervoltage = -30% to 25% of maximum rated input voltage1

Operating value

100% operation at set value

Reset (HYS.)

Hysteresis

5% of operating value (fixed)

Resetting method

Automatic reset

Operating time (T)

Overvoltage/undervoltage

0.1 to 30 s

Phase-sequence, phase-loss

0.1 s max.

Power ON lock (LOCK)

1 s or 5 s (Changed with the DIP switch)

Overload capacity

Continuous input at 115% of maximum input, 10 s at 125% (up to 600 VAC)

Repeat accuracy

Operating value

±0.5% full scale (at 25°C and an ambient humidity of 65% at the rated power supply voltage, DC or 50/60 Hz sine wave input)

Operating time

±50 ms (at 25°C and 65% humidity, rated power supply voltage)

Indicators

Power (PWR): Green LED, relay output (RY): Yellow LED, alarm outputs (ALM 1/2): Red LED

Applicable standards

Conforming standards

EN 60947-5-1
Installation environment (pollution level 2, installation category III)

EMC

EN 60947-5-1

Safety standards

UL 508 (Recognition), Korean Radio Waves Act (Act 10564), CSA and CCC

Size in mm (H × W × D)

90 × 22.5 × 100


1. The rated input voltage is switched with a switch

1. The rated input voltage is switched with a switch

Har du et spørsmål?

Vi er klare til å hjelpe.

Kontakt oss

Abonner på produktoppdateringer

Nyhetsbrev om produkter, løsninger og tjenester, direkte i innboksen.

Takk for at du abonnerer på Omrons eNews. Du vil snart motta en e-post fra oss. Denne e-posten inneholder en link som aktiverer ditt abonnement. Denne metoden brukes på grunn av juridiske årsaker og til å se til at ingen kan misbruke din e-postadresse.

Vi har for tiden tekniske problemer. Ditt skjema har ikke blitt innsendt. Vi beklager så mye og håper du vil prøve igjen senere. Detaljer:

Download

Produktdokumentasjon

Last ned dataark, håndbøker og brosjyrer.

Bla gjennom nedlastingssenter

Opplæringskurs

Få opplæring fra våre beste ingeniører. Fra nybegynner til avansert nivå.

Vis opplæringskurs